| MODEL | UVS1.0K-1L | UVS1.5K-1L |
| INPUT | Voltage | 120V |
| Voltage Range | +10%, -25% |
| Frequency | 50/60Hz ± 2% with line sync enabled. 50/60/400Hz ,
47-450Hz with line sync disabled |
| Current | 11A |
14A |
| OUTPUT | Voltage | 120VAC |
| VA |
1000 |
1500 |
| WATTS | 700 | 1050 |
| Frequency | 50/60Hz |
| Voltage
Regulation | ± 3% |
| Frequency
Stability | 50/60Hz ± 1.5Hz With Line Sync enabled.
50/60Hz ± 0.5Hz With Line Sync disabled. 50/60Hz ± .01Hz with Line Sync disabled
and Crystal Option |
| Dynamic
Response | <0.5ms recovery time typical |
| Harmonic
Distortion | <3% @ full linear load <5% @ non-linear load |
| Current |
8.3A |
12.5 |
| Protection | Short circuit & overload, Overheating, Excessive battery
discharge |
| OPTIONS | Dedicated
DC Input (DC to AC Converter) |
48 VDC |
72 VDC |
| Remote
Alarm and Indicator Kit | Provides Visual & Audible Operational Status |
| Frequency
Conversion | 60/50; 50/60 Hz |
| High
Inrush | Momentary Bypass for excessive Start-Up Surges |
| EFFICIENCY | AC
to AC | 83% Typical. |
| Ride
Through Time | @
350 Watts | 132 ms typ. | 170 ms typ. |
| Audible Noise | @
5 Feet | 49 dBA (800-1.5KVA) 54 dBA (2VA) |
| Indicators (LED's) | Single | Utility Present, Inverter On, Summary Alarm |
| Sequenced | Load Level, Battery Level |
| Alarms | Audible | Utility Interrupt, Overload, Inverter Failure, Low Battery |
| Interface | Computer | Dry Contact Closures |
| Environment | Temperature | 0C- 40C (32F-104F) |
| Humidity | 10%-90% Non-condensing |
| Mechanical | Input
Line |
5-15P |
5-20P |
| Output
5-15R (Qty) |
UVS (4) |
UVS (4) |
| Weight
Lbs. (kg) |
17 (7.7) |
21.0 (9.6) |
| Dimensions
inches (cm) H x W x D |
3.5 x 15 x 17.0 (38 x 28 x17) |
17.5 x 11 x 21 (38x 28 x 9.6) |
| Approvals | Agency | UL Listed |